Reverse Osmosis (RO)
High-pressure membrane separation achieving 95-99.5% salt rejection through solution-diffusion mechanism, producing high-purity permeate for water reuse, desalination, and industrial applications at 10-70 bar depending on feed salinity.
Overview
Reverse osmosis (RO) is the tightest membrane process, capable of removing dissolved salts, organics, and essentially all suspended and colloidal matter. RO operates by applying pressure greater than the osmotic pressure of the feed solution, forcing water through a semi-permeable membrane while retaining >95% of dissolved solids. This technology enables drinking water production from seawater, brackish water, and wastewater reuse for potable and industrial applications.
When to Use
- Seawater desalination (TDS 35,000-45,000 mg/L → <500 mg/L)
- Brackish water desalination (TDS 1,500-10,000 mg/L → <250 mg/L)
- Direct and indirect potable reuse (wastewater → drinking water)
- Ultrapure water production (pharmaceutical, electronics, power generation)
- Industrial process water (boiler feed, semiconductor manufacturing)
- Zero liquid discharge (ZLD) concentration step
- Heavy metal removal (>99% for most metals)
- Nitrate removal (>95%)
- Organic micropollutant removal (>95% for most compounds)
Key Characteristics
- Salt rejection: 95-99.5% (brackish water), 99-99.7% (seawater)
- Operating pressure: 10-25 bar (brackish), 55-70 bar (seawater)
- Permeate flux: 15-25 LMH (brackish), 10-15 LMH (seawater)
- Recovery: 75-85% (brackish), 40-50% (seawater)
- Permeate TDS: <250 mg/L (brackish), <500 mg/L (seawater)
- Boron rejection: 70-90% (standard), >95% (high rejection membranes)
- TOC rejection: 95-99%
- Silica rejection: 95-98%
- Energy: 0.8-1.5 kWh/m³ (brackish with ERD), 3-5 kWh/m³ (seawater with ERD)
Operating Modes
Basic Mode
- Constant pressure operation
- Fixed recovery ratio
- Simple solution-diffusion model (default rejection coefficients)
- Concentrate to drain
- Basic scaling prediction (Langelier Saturation Index)
Advanced Mode
- Solution-diffusion model with concentration polarization correction
- Multi-stage configuration (two-pass for ultrapure water)
- Detailed scaling prediction (Stiff-Davis, ROSA/WAVE software)
- Antiscalant optimization
- Energy recovery device (ERD) simulation: pressure exchanger or turbocharger
- Brine management: ZLD, deep well injection, evaporation
- Membrane aging simulation (salt passage increase over time)
- Cleaning frequency prediction
Mathematical Model
Solution-Diffusion Model
Water flux:
$$J_w = A \times (\Delta P - \Delta \pi)$$
Where:
- $J_w$ = water flux (L/m²·h or m/s)
- $A$ = water permeability coefficient (L/m²·h·bar)
- $\Delta P$ = transmembrane pressure (bar)
- $\Delta \pi$ = osmotic pressure difference (bar)
For RO, reflection coefficient $\sigma \approx 1.0$ (near-perfect semi-permeable membrane).
Solute flux:
$$J_s = B \times \Delta C$$
Where:
- $J_s$ = solute flux (g/m²·s)
- $B$ = solute permeability coefficient (m/s)
- $\Delta C$ = concentration difference (g/m³)
Observed rejection:
$$R = 1 - \frac{C_p}{C_f} = \frac{A \times (\Delta P - \Delta \pi)}{A \times (\Delta P - \Delta \pi) + B}$$
Osmotic Pressure
Van't Hoff equation for multi-component solutions:
$$\pi = \sum_i i \times M_i \times R \times T$$
Simplified for TDS:
$$\pi [bar] \approx 0.00075 \times TDS [mg/L]$$
Examples:
- Brackish water (TDS 2,000 mg/L): π ≈ 1.5 bar
- Brackish water (TDS 5,000 mg/L): π ≈ 3.75 bar
- Seawater (TDS 35,000 mg/L): π ≈ 26 bar
- Brine (TDS 70,000 mg/L): π ≈ 53 bar
Net driving pressure:
$$\Delta P_{net} = \Delta P_{applied} - (\pi_{concentrate} - \pi_{permeate})$$
Key insight: As recovery increases, concentrate TDS and π increase, requiring higher applied pressure.
Recovery and Concentration Factor
Recovery:
$$Y = \frac{Q_p}{Q_f} \times 100%$$
Concentration factor:
$$CF = \frac{1}{1 - Y} = \frac{C_{concentrate}}{C_{feed}}$$
Examples:
- Y = 75% → CF = 4× (concentrate is 4× more concentrated than feed)
- Y = 80% → CF = 5×
- Y = 50% (seawater) → CF = 2×
Concentrate TDS:
$$TDS_{concentrate} = \frac{TDS_{feed} - Y \times TDS_{permeate}}{1 - Y}$$
For high rejection (R > 0.98):
$$TDS_{concentrate} \approx \frac{TDS_{feed}}{1 - Y}$$
Concentration Polarization
Solute accumulation at membrane surface:
$$\frac{C_{wall}}{C_{bulk}} = \exp\left(\frac{J_w}{k}\right)$$
Where $k$ = mass transfer coefficient (2-6 × 10⁻⁵ m/s for RO)
Effect of concentration polarization:
- Increases local osmotic pressure by 10-30%
- Reduces flux
- Promotes scaling
Mitigation:
- High crossflow velocity (turbulence)
- Feed spacers (channel height 0.7-1.0 mm)
- Lower flux operation
Scaling Prediction
Common scalants:
Calcium carbonate (CaCO₃):
- Langelier Saturation Index (LSI): $$LSI = pH - pH_s$$
- Scale risk if LSI > 0
- Control: Acid dosing (lower pH to 6.5-7.0), antiscalant
Calcium sulfate (CaSO₄·2H₂O, gypsum):
- Saturation level (% of solubility): $$SL_{CaSO_4} = \frac{[Ca^{2+}] \times [SO_4^{2-}]}{K_{sp}}$$
- Scale risk if SL > 100% (with antiscalant, allow up to 200-250%)
- Often limits recovery in brackish water RO
Barium sulfate (BaSO₄):
- $K_{sp}$ = 1.1 × 10⁻¹⁰ (extremely low)
- Even trace Ba²⁺ can cause scaling
- Must remove Ba²⁺ upstream (ion exchange, NF)
Silica (SiO₂):
- Colloidal and reactive silica
- Solubility: 120-150 mg/L (amorphous, pH 7-8)
- Forms metal silicates (difficult to clean)
- Limit concentrate silica to <120 mg/L or use specialized antiscalant
Strontium sulfate (SrSO₄):
- Similar to CaSO₄, but less common
Membrane Fouling
Types of fouling:
- Scaling (inorganic): CaCO₃, CaSO₄, silica, BaSO₄
- Colloidal: Clays, metal hydroxides (Fe, Al, Mn)
- Organic: Humic acids, oils, surfactants
- Biological: Bacteria, biofilms (polysaccharides)
Silt Density Index (SDI):
Measure of colloidal fouling potential:
$$SDI = \frac{100 \times (1 - t_i / t_f)}{T}$$
Where:
- $t_i$ = initial time to collect 500 mL
- $t_f$ = final time to collect 500 mL (after T minutes)
- $T$ = test duration (typically 15 min)
Requirement: SDI₁₅ < 3 for RO feed (preferably <2)
Temperature Correction
Viscosity and permeability change with temperature:
$$J_T = J_{25°C} \times TCF$$
Where $TCF$ = temperature correction factor:
$$TCF = \exp\left[2640 \times \left(\frac{1}{298} - \frac{1}{T_K}\right)\right]$$
Simplified:
$$J_T \approx J_{25} \times 1.03^{(T-25)}$$
Example:
J₂₅ = 20 LMH @ 25°C
J₁₅ = 20 × 1.03⁻¹⁰ = 14.8 LMH @ 15°C (26% reduction!)
J₃₅ = 20 × 1.03¹⁰ = 26.9 LMH @ 35°C (35% increase)Critical for design: Always normalize flux to 25°C for performance evaluation.
Design Parameters
Brackish Water RO (BWRO)
| Parameter | Symbol | Unit | Range | Default | Description |
|---|---|---|---|---|---|
| Feed TDS | - | mg/L | 1,500-10,000 | 3,000 | Total dissolved solids |
| Operating pressure | $\Delta P$ | bar | 10-25 | 15 | Applied pressure |
| Temperature | $T$ | °C | 10-30 | 25 | Feed water temperature |
| Design flux | $J_w$ | LMH | 15-25 | 20 | Permeate flux @ 25°C |
| Recovery | $Y$ | % | 70-85 | 75 | Water recovery ratio |
| Salt rejection | $R$ | % | 97-99.5 | 98.5 | TDS rejection |
| Permeate TDS | - | mg/L | 50-300 | 150 | Product water TDS |
Seawater RO (SWRO)
| Parameter | Symbol | Unit | Range | Default | Description |
|---|---|---|---|---|---|
| Feed TDS | - | mg/L | 30,000-45,000 | 35,000 | Seawater TDS |
| Operating pressure | $\Delta P$ | bar | 55-70 | 60 | High pressure |
| Temperature | $T$ | °C | 15-30 | 20 | Seawater temperature |
| Design flux | $J_w$ | LMH | 10-15 | 12 | Permeate flux @ 25°C |
| Recovery | $Y$ | % | 35-50 | 45 | Lower recovery (high π) |
| Salt rejection | $R$ | % | 99.2-99.7 | 99.5 | High rejection |
| Permeate TDS | - | mg/L | 200-500 | 400 | Potable water limit: 500 mg/L |
Configuration Guide
Step-by-Step Setup (Brackish Water RO)
Feed Water Analysis
Minimum required parameters:
- TDS, pH, temperature, alkalinity
- Hardness (Ca²⁺, Mg²⁺), sulfate, chloride, silica
- Barium (critical, even at trace levels)
- Iron, manganese (oxidation/fouling risk)
- TOC (organic fouling potential)
- SDI₁₅ (colloidal fouling)
Example feed water: TDS = 2,500 mg/L, pH = 7.6, T = 20°C Ca²⁺ = 120 mg/L, SO₄²⁻ = 350 mg/L Silica = 35 mg/L, Ba²⁺ = 0.05 mg/L (trace) SDI₁₅ = 2.5Select Recovery
Limited by scaling:
Calculate concentrate composition at various recoveries: Y = 75%: Concentrate Ca²⁺ = 120 / 0.25 = 480 mg/L Concentrate SO₄²⁻ = 350 / 0.25 = 1,400 mg/L Concentrate silica = 35 / 0.25 = 140 mg/L (above 120 mg/L limit) Y = 70%: Concentrate silica = 35 / 0.30 = 117 mg/L ✓ (below limit) Check CaSO₄: Use scaling software (ROSA, WAVE) With antiscalant, Y = 75-80% may be achievable Use Y = 75% with silica antiscalantEstimate Osmotic Pressure
Feed: π_f = 0.00075 × 2,500 = 1.875 bar Permeate (98.5% rejection): TDS_p = 2,500 × 0.015 = 37.5 mg/L π_p = 0.00075 × 37.5 = 0.03 bar ≈ 0 (negligible) Concentrate (Y=75%): TDS_c = 2,500 / 0.25 = 10,000 mg/L π_c = 0.00075 × 10,000 = 7.5 bar Average π (concentrate avg ≈ feed + concentrate / 2): π_avg ≈ (1.875 + 7.5) / 2 = 4.7 barSelect Operating Pressure
$$\Delta P = \pi_{avg} + \Delta P_{margin}$$
ΔP = 4.7 + 5 = 9.7 bar (margin for flux and pressure drop) Use ΔP = 15 bar (standard BWRO, provides good margin) Net driving pressure = 15 - 4.7 = 10.3 barEstimate Flux
Manufacturer's data, but typical:
A = 1.5 LMH/bar (typical BWRO membrane @ 25°C) J_w = A × ΔP_net = 1.5 × 10.3 = 15.5 LMH Temperature correction (20°C): J_20 = 15.5 × 1.03⁻⁵ = 13.3 LMH Use J = 20 LMH for design (assumes 25°C normalized, or increase ΔP)Calculate Membrane Area
Q_permeate = 5,000 m³/d = 208 m³/h J = 20 LMH A = 208 × 1000 / 20 = 10,400 m² Standard 8"×40" BWRO elements: 37 m² each Total elements = 10,400 / 37 = 281 elements Configuration: 47 pressure vessels × 6 elements = 282 elements (10,434 m²)Pretreatment Requirements
Essential for RO feed:
- Cartridge filter: 5 μm absolute, protect from particles
- SDI reduction: ❤️ required, <2 preferred
- Options: UF/MF (best), multimedia filter, coagulation + sedimentation
- Dechlorination: Free Cl₂ <0.05 mg/L (polyamide membrane damage)
- Sodium metabisulfite: 3× stoichiometric dose
- Antiscalant: 3-5 mg/L, inhibit CaSO₄, CaCO₃, silica scaling
- Acid dosing (optional): Lower pH to 6.5-7.0 for CaCO₃ control
Energy Recovery Device (ERD)
For BWRO >10 bar, ERD recommended:
Pressure exchanger (isobaric):
- Efficiency: 94-97%
- No rotating seals, low maintenance
- Most common for large SWRO and BWRO >15 bar
Turbocharger (Pelton wheel):
- Efficiency: 80-88%
- Simpler, lower cost
- Suitable for BWRO 10-20 bar
Example (pressure exchanger, 95% efficiency): Q_concentrate = 5,000 / 0.75 - 5,000 = 1,667 m³/d = 69.4 m³/h Pressure recovered ≈ 14 bar (near feed pressure) Power recovered = 69.4 × 14 × 10⁵ × 0.95 / 3600 = 25.5 kWCalculate Energy Consumption
High-pressure pump (without ERD):
Q_feed = 5,000 / 0.75 = 6,667 m³/d = 278 m³/h ΔP = 15 bar η_pump = 0.80 Power = (278 × 15 × 10⁵) / (0.80 × 3600) = 145 kW Daily energy = 145 × 24 = 3,480 kWh/d Specific energy = 3,480 / 5,000 = 0.70 kWh/m³With ERD (95% efficiency):
Net power = 145 - 25.5 = 119.5 kW Daily energy = 119.5 × 24 = 2,868 kWh/d Specific energy = 0.57 kWh/m³ (18% savings)Chemical Dosing
Antiscalant:
Dose = 4 mg/L (feed) Daily = 6,667 × 4 × 10⁻³ = 26.7 kg/d Annual = 9,746 kg/year Cost @ $5/kg = $48,730/yearDechlorination (sodium metabisulfite):
Feed Cl₂ = 0.5 mg/L (from upstream chlorination) Na₂S₂O₅ dose = 3 × 0.5 / 0.35 = 4.3 mg/L (35% purity) Daily = 6,667 × 4.3 × 10⁻³ = 28.7 kg/d Annual = 10,475 kg/year Cost @ $2/kg = $20,950/year
Typical Design Values
| Application | Feed TDS (mg/L) | Pressure (bar) | Flux (LMH) | Recovery (%) | Permeate TDS (mg/L) | Energy (kWh/m³) |
|---|---|---|---|---|---|---|
| Low brackish | 1,500-3,000 | 10-15 | 18-25 | 75-85 | 30-100 | 0.5-0.8 (w/ ERD) |
| High brackish | 5,000-10,000 | 18-25 | 15-22 | 70-80 | 100-250 | 1.0-1.5 (w/ ERD) |
| Seawater | 35,000-38,000 | 55-65 | 10-15 | 40-50 | 300-500 | 3.0-4.5 (w/ ERD) |
| High-salinity seawater | 40,000-45,000 | 65-70 | 8-12 | 35-45 | 400-500 | 4.5-6.0 (w/ ERD) |
| Wastewater reuse | 800-2,000 | 10-15 | 15-20 | 75-85 | 20-80 | 0.5-0.8 (w/ ERD) |
Performance Criteria
Salt Rejection
| Ion | Brackish RO | Seawater RO |
|---|---|---|
| Na⁺, Cl⁻ | 95-99% | 99-99.7% |
| Ca²⁺, Mg²⁺ | 97-99.5% | 99.5-99.8% |
| SO₄²⁻ | 99-99.9% | 99.8-99.9% |
| NO₃⁻ | 93-97% | 97-99% |
| F⁻ | 94-97% | 97-99% |
| Boron (B(OH)₃) | 70-90% | 70-90% (pH-dependent) |
| Silica | 95-98% | 97-99% |
| TOC | 95-99% | 97-99.5% |
Boron removal:
- At pH 7-8: 70-85% rejection (uncharged boric acid)
- At pH >9: >95% rejection (charged borate ion)
- For drinking water (<1 mg/L B): Use high-boron-rejection membranes or two-pass RO
Comparison: BWRO vs. SWRO
| Parameter | Brackish Water RO | Seawater RO |
|---|---|---|
| Feed TDS | 1,500-10,000 mg/L | 30,000-45,000 mg/L |
| Osmotic pressure | 1-8 bar | 25-35 bar |
| Operating pressure | 10-25 bar | 55-70 bar |
| Salt rejection | 97-99.5% | 99.2-99.7% |
| Recovery | 70-85% | 35-50% |
| Flux | 15-25 LMH | 10-15 LMH |
| Energy (w/ ERD) | 0.5-1.5 kWh/m³ | 3.0-5.0 kWh/m³ |
| Membrane elements | Standard pressure | High pressure (thicker) |
| Pretreatment | Standard (SDI<3) | More rigorous (SDI<2) |
| Scaling risk | Moderate (CaSO₄) | Lower (dilution by water) |
| Brine disposal | Easier (lower volume) | Challenging (high volume, salinity) |
Troubleshooting
| Issue | Cause | Solution |
|---|---|---|
| Flux decline (normalized) | Membrane fouling (organic, colloidal) | CIP with caustic + surfactant |
| Scaling (CaCO₃, CaSO₄, silica) | CIP with acid, increase antiscalant dose | |
| Biological fouling | CIP with biocide, improve pretreatment | |
| Membrane compaction (aging) | Accept gradual decline, plan replacement | |
| Salt passage increase | Membrane degradation (chlorine, oxidation) | Improve dechlorination, replace elements |
| High temperature | Cool feed, check permeate TDS trend | |
| Seal leak (O-ring) | Inspect and replace O-rings | |
| Membrane aging (end of life) | Replace membranes (typically 3-7 years) | |
| High differential pressure | Particulate fouling (lead elements) | CIP, improve pretreatment, check SDI |
| Biological fouling | Biocide treatment, chlorination of pretreatment | |
| Scale buildup | Acid cleaning, optimize antiscalant | |
| Low recovery | Concentrate pressure too low | Check ERD operation, increase feed flow |
| Scaling concern (over-conservative) | Scaling analysis, optimize recovery | |
| High permeate TDS | Low feed pressure | Increase pressure to design value |
| Temperature spike | Normal, verify normalized salt passage | |
| Membrane damage | Integrity test, replace faulty elements | |
| Excessive CIP frequency (❤️ months) | Poor pretreatment (high SDI) | Improve UF/MF, multimedia filter |
| Organic fouling | Upstream TOC removal (GAC, ozone) | |
| Flux too high | Reduce flux by 10-20% | |
| Permeate hardness (bypass) | O-ring leak | Inspect seals, pressure test |
| Membrane glue line failure | Replace element | |
| Pressure drop in ERD | Fouling in ERD | Clean ERD, improve feed filtration |
| Mechanical wear | Inspect and repair/replace |
Operation & Maintenance
Continuous Monitoring (SCADA)
- Feed, concentrate, permeate flow rates
- Feed, interstage, and permeate pressure
- Permeate conductivity (TDS)
- Temperature (normalize performance)
- Differential pressure (fouling indicator)
- Normalized flux and salt passage (correct for T, ΔP)
Daily Checks
- Review normalized flux (flag if <10% decline from baseline)
- Check normalized salt passage (flag if >10% increase)
- Verify antiscalant injection rate
- Check dechlorination (free Cl₂ <0.05 mg/L in RO feed)
- Measure differential pressure (scaling/fouling trend)
- Inspect for leaks
- Review ERD operation (if equipped)
Weekly Maintenance
- Lab analysis: Feed, permeate, concentrate TDS and major ions
- SDI test on RO feed (target: ❤️, preferably <2)
- Calibrate conductivity probes
- Check cartridge filter differential pressure (replace if >1 bar)
- Review chemical tank levels
- Scaling potential calculation (update water quality)
Monthly Tasks
- Detailed performance normalization (flux, salt passage, ΔP, T correction)
- Fouling/scaling analysis (compare to baseline)
- Pretreatment performance review (UF/MF integrity)
- Inspect high-pressure pump
- Antiscalant effectiveness (check scaling indices)
- Energy consumption analysis
- Plan CIP if normalized flux declined >10-15%
Quarterly/CIP Events
- Full CIP protocol:
- Low pH (acid): Remove CaCO₃, CaSO₄, metal hydroxides
- High pH (caustic + surfactant): Remove organics, biofilm, silica
- Biocide (if biofouling): Sodium hypochlorite (check compatibility)
- Post-CIP performance test (flux recovery target: >95%)
- Replace fouled/damaged elements
- Membrane autopsy (if chronic fouling, send to manufacturer)
- Calibrate all instruments
- Review operating conditions and optimize
Annual Tasks
- Comprehensive performance audit (compare to design)
- Membrane element inspection (open pressure vessels)
- Replace cartridge filters (preventive, all housings)
- ERD overhaul (if equipped): Inspect, replace wear parts
- High-pressure pump seal replacement (preventive)
- Scaling/fouling trend analysis (multi-year)
- Membrane life assessment (plan replacement, typically 3-7 years)
- Brine disposal compliance (environmental permits)
- Cost-benefit analysis: Energy, chemicals, membranes
- Consider process improvements (staged RO, two-pass, etc.)
Advanced Features
Two-Pass RO (Ultrapure Water)
First pass: Standard BWRO (TDS reduction to 50-200 mg/L) Second pass: Polish to <1 mg/L TDS (ultrapure water)
Applications:
- Pharmaceutical manufacturing
- Semiconductor fabrication
- Power plant boiler feed
- Laboratory-grade water
Benefits:
- Permeate TDS <1 mg/L (resistivity >15 MΩ·cm)
- TOC <10 ppb
- Silica <10 ppb
- Bacteria <1 cfu/mL
Staged RO (Maximize Recovery)
Two-stage configuration:
- Stage 1: 6 pressure vessels × 6 elements (primary production)
- Stage 2: 2 pressure vessels × 6 elements (treat Stage 1 concentrate)
Recovery boost:
- Single-stage: 75%
- Two-stage: 75% + (25% × 50%) = 87.5% overall
Interstage booster pump: Required to overcome Stage 2 osmotic pressure
Seawater RO with ERD
Energy recovery device essential:
- Concentrate pressure: 55-60 bar
- Concentrate flow: 50-60% of feed (50-65% recovery)
- Energy recovery: 94-97% (pressure exchanger)
Specific energy breakdown (SWRO, 45% recovery):
Theoretical minimum = π × ln(1/(1-Y)) = 26 × ln(1/0.55) = 15.6 bar·m³/m³ = 0.43 kWh/m³
Actual with ERD:
- High-pressure pump: 55 bar
- ERD recovers: 95% of 55 bar × 55% flow = 28.7 bar·m³/m³
- Net energy: 55 - 28.7 = 26.3 bar·m³/m³ = 0.73 kWh/m³
- Inefficiencies (pumps, motors, piping): ×1.3
- Total: 0.95 kWh/m³
Add pretreatment (intake, UF): +0.5 kWh/m³
Add post-treatment (remineralization, disinfection): +0.2 kWh/m³
Total SWRO plant: 1.65 kWh/m³ (state-of-the-art)
Older plants without ERD: 6-10 kWh/m³Brine Concentrate Management
Disposal options:
Surface water discharge:
- Requires mixing zone analysis (dilution modeling)
- Salinity impact on aquatic life
- Thermal discharge consideration (SWRO)
Deep well injection:
- Geological suitability (confined aquifer)
- Regulatory approval (UIC permit)
- Monitor groundwater quality
Sewer discharge:
- Municipal approval required
- Volume and TDS limits
- Discharge fees
Evaporation ponds:
- Arid climates only (high evaporation rate)
- Large land area required
- Crystallized salts disposal
Zero Liquid Discharge (ZLD):
- Brine concentrator (additional RO, thermal, MVC)
- Crystallizer (evaporate final brine to solid salts)
- High cost: $5-20/m³ concentrate
- Solid salt disposal or beneficial use
Beneficial reuse:
- Dust suppression (roads, mining)
- Industrial processes (cooling towers, process water)
- Salt production (selective crystallization)
Hybrid Processes
RO + Thermal (MSF/MED):
- RO produces 60-70% of freshwater (low energy)
- Thermal desalination treats RO concentrate (high recovery)
- Common in Middle East (energy-rich regions)
RO + Ion Exchange:
- RO bulk TDS removal
- IX polish final product (ultrapure water)
NF + RO:
- NF softening (remove hardness)
- RO operates at higher recovery (no CaSO₄ scaling)
Worked Example: Brackish Water RO Plant
Given
- Flow: 10,000 m³/d permeate (average)
- Feed water: TDS = 3,500 mg/L, Ca²⁺ = 150 mg/L, SO₄²⁻ = 450 mg/L, Silica = 40 mg/L, pH = 7.8, T = 22°C, SDI₁₅ = 3.5
- Target: Permeate TDS <200 mg/L, potable water reuse
- Include pretreatment, antiscalant, ERD
Solution
Step 1: Pretreatment Design
SDI = 3.5 > 3.0 (too high for RO)
Pretreatment: UF (0.04 μm) to reduce SDI to <2
- UF flux: 60 LMH, Recovery: 93%
- UF area = 10,000 / 0.93 / 60 / 24 = 7,491 m² (125 modules × 60 m²)
- UF energy: 0.06 kWh/m³ × 10,753 m³/d = 645 kWh/d
Dechlorination: Sodium metabisulfite (assume 0.8 mg/L Cl₂ in UF feed)
- Dose: 3 × 0.8 / 0.35 = 6.9 mg/L
- Daily: 10,753 × 6.9 × 10⁻³ = 74.2 kg/dStep 2: Select RO Recovery
Check silica limit (120 mg/L in concentrate):
Y_max = 1 - (40 / 120) = 66.7%
Check CaSO₄ scaling (use software, simplified here):
Y = 75% → Concentrate SO₄²⁻ = 450 / 0.25 = 1,800 mg/L (likely to scale)
Y = 70% → Concentrate SO₄²⁻ = 450 / 0.30 = 1,500 mg/L (with antiscalant, acceptable)
Use Y = 75% with silica-compatible antiscalant (assume effective)Step 3: Calculate Osmotic Pressures
Feed: π_f = 0.00075 × 3,500 = 2.625 bar
Permeate (98.5% rejection): π_p ≈ 0 bar
Concentrate: TDS_c = 3,500 / 0.25 = 14,000 mg/L
π_c = 0.00075 × 14,000 = 10.5 bar
Average: π_avg ≈ (2.625 + 10.5) / 2 = 6.6 barStep 4: Operating Pressure and Flux
ΔP = 18 bar (standard BWRO, provides 18 - 6.6 = 11.4 bar net driving pressure)
Temperature correction factor (22°C):
TCF = 1.03^(22-25) = 0.913
Flux @ 25°C: J₂₅ = 1.5 × 11.4 = 17.1 LMH
Flux @ 22°C: J₂₂ = 17.1 × 0.913 = 15.6 LMH
Use J = 20 LMH for design (conservative, allows fouling margin)Step 5: Membrane Area
Q_permeate = 10,000 m³/d = 417 m³/h
A = 417 × 1000 / 20 = 20,850 m²
Elements (37 m²/element): 20,850 / 37 = 563 elements
Configuration: 94 pressure vessels × 6 elements = 564 elements (20,868 m²)
Organize in 2 trains for redundancy: 47 vessels per trainStep 6: Antiscalant Dosing
Dose: 5 mg/L (feed, silica-compatible formulation)
Q_feed = 10,000 / 0.75 = 13,333 m³/d
Daily: 13,333 × 5 × 10⁻³ = 66.7 kg/d
Annual: 24,346 kg/year
Cost @ $5/kg = $121,730/yearStep 7: Energy Consumption
High-pressure pump:
Q_feed = 13,333 m³/d = 556 m³/h
Power = (556 × 18 × 10⁵) / (0.80 × 3600) = 348 kW
ERD (pressure exchanger, 95% efficiency):
Q_concentrate = 3,333 m³/d = 139 m³/h
Pressure recovered = 17 bar
Power recovered = 139 × 17 × 10⁵ × 0.95 / 3600 = 62.2 kW
Net RO power = 348 - 62.2 = 285.8 kW
Daily RO energy = 285.8 × 24 = 6,859 kWh/d
RO specific energy = 0.69 kWh/m³
Total plant (RO + UF + misc):
Total = 6,859 + 645 + 200 = 7,704 kWh/d
Specific energy = 0.77 kWh/m³
Annual energy cost @ $0.12/kWh = 7,704 × 365 × 0.12 = $337,686/yearStep 8: Operating Cost Summary
Energy: $337,686/year
Antiscalant: $121,730/year
Dechlorination: $54,200/year (74.2 kg/d × $2/kg)
UF membranes (7-year life): $300,000 / 7 = $42,857/year
RO membranes (5-year life): $700,000 / 5 = $140,000/year
UF + RO CIP chemicals: $10,000/year
Cartridge filters: $20,000/year
Maintenance: $50,000/year
Total: $776,473/year = $0.21/m³ producedRelated Units
- Nanofiltration - Lower pressure, partial desalination
- Ultrafiltration - RO pretreatment
- UV-Disinfection - Post-treatment disinfection
- Chemical-Dosing - Antiscalant, dechlorination, acid
- Remineralization - Post-RO stabilization
References
- Crittenden, J.C. et al. (2012). MWH's Water Treatment, 3rd Ed., Ch. 12: Reverse Osmosis.
- AWWA (2011). Water Quality and Treatment, 6th Ed., Ch. 12: RO and Nanofiltration.
- Baker, R.W. (2012). Membrane Technology and Applications, 3rd Ed., Wiley, Ch. 4.
- WEF (2018). Design of Municipal Wastewater Treatment Plants, MOP 8, 6th Ed., Ch. 17.
- Voutchkov, N. (2013). Desalination Engineering: Planning and Design, McGraw-Hill.
- US EPA (2012). Guidelines for Water Reuse, EPA/600/R-12/618.
- IDA (2023). Desalination Yearbook 2022-2023, International Desalination Association.