Wastewater Pumping Station (Engineered Unit) ​

A wet well with submersible pumps on a common rising main — the first engineered unit, and the one whose generated content is most complete.

Which simulation? Running this unit uses the client-side, PLC-style scan simulation in your browser, not the server-side biokinetic process simulation. See Which "simulation" this section is about.

Slugww-pumping-station
Name in the libraryWastewater Pumping Station (Engineered Unit)
CategoryProcess Units/engineered
Seededversion 0.6.0, maturity published
Interface points3 — inlet, outlet, signals
Asked on drop9 for a new station, 14 for an existing one
Editable setpoints16
Fault catalogue13 cases, filtered to what is fitted

What it models ​

A wastewater pumping station: a wet well, one to six submersible pumps with up to two held as standby, a common rising main to a receiving chamber, and control panel CP-01.

The drawing it generates carries the wet well, the pumps and their drives, the non-return and isolation valve each branch's fittings call for, the level transmitter LT-101, the high-high and low-low floats LSHH / LSLL, the flow meter FT-101, the air valve, the emergency storage tank and the panel. Tags take their leading digit from the station's area number, so a second station on the same drawing is LT-201, P-201, CP-02 and does not collide.

The plant model integrated during a run is the wet well's water balance — inflow against what the running pumps deliver through the rising main at the head the system curve gives — together with the instruments that read it (including the possibility that they read it wrongly) and the pumps' mechanical state.

Key parameters ​

Asked on drop ​

Nine always, and five more when the station is an existing one — the figures you would survey on an asset that is already there rather than derive for one that is not.

ParameterUnitTypeAsked
Design basis—new / existingalways
Dry weather flowl/snumberalways
Design peak flowl/snumberalways
Static headmnumberalways
Rising main lengthmnumberalways
Pumps installedcount1–6always
Pumps held as standbycount0–2always
Drive type—variable-speed drive / direct on linealways
Control strategy—level / flow / on-offalways
Rising main internal diametermmnumberif existing
Pump duty flowl/snumberif existing
Pump duty headmnumberif existing
Pump shut-off headmnumberif existing
Wet well plan aream²numberif existing

Everything else — the main material, the instrument set, the itemised branch fittings, the overflow level, the surveyed wall roughness and pump efficiency — keeps the template's default. Four of those defaults are the instruments, expressed as four separate yes/no parameters (LT, LSHH, LSLL, FT) because the parameter system has no set type; none of them is asked on drop.

Editable setpoints (in the workspace) ​

Sixteen, grouped in the Simulate view by the loop whose node owns them:

SetpointUnit
Stop level · PID setpoint · Duty start · Assist stop · Assist start · Last assist startm
Minimum speed · No-flow check aboveHz
No-flow threshold per pump · Pass-forward flow setpointl/s
No-flow delay · Fail-to-start time · Auto reset afters
Low-low float hardwired to drive safe-torque-off · FT fault inhibits no-flow check · Assist pumps stop one at a timeyes/no

A setpoint that does not apply to your configuration is hidden rather than disabled — because the control node that owned it was not generated either. Choose direct-on-line over a variable-speed drive and the minimum-speed setpoint goes away with the node that read it.

The high-high and low-low float levels and the starts-per-hour allowance are deliberately not setpoints: the float levels are survey data, and the starts allowance comes from the rule set.

Control loops ​

Six families of generated graph, in scan order:

wet well → selector → each pump (one per installed pump) → floats (hardwired) → rising main → outstation

The float circuit runs even when the PLC is not energised — which is the whole reason it is generated as a graph rather than described in prose.

What the outputs mean ​

Published port values ​

PortWhat it publishes
inletThe flows the station is designed for — dry weather and design peak
outletThe maximum it passes forward, with the rising main's bore and the head at it
signalsThe size of its signal set

For the reference configuration those read 4.0 / 12.0 l/s at the inlet, ≤ 12.0 l/s · DN100 · 10.5 m at the outlet and 37 signals.

Overview figures ​

Arrangement, control method, duty point of one pump, station capacity, rising main bore and material, motor rating, the number of design findings, and the number of control loops.

Live facts during a run ​

Titled Station: the clock, the wet-well level with the transmitter's reading beside it, in/out flows, the state of each pump, starts per hour, and the volume spilled.

Trend panels ​

Three: level (with the LT reading dashed over it, and reference lines at the overflow level, LSHH, duty start, stop and LSLL), flow (inflow and the flow meter), and pumps running.

The I/O schedule ​

Every point exists because a piece of the configuration exists: the level transmitter brings one analogue input; each pump brings five digital inputs, two digital outputs, one analogue output and two analogue inputs; the panel is sized from the totals plus the rule set's spare allowance. That is what makes the reference station exactly 37 points — 20 DI, 6 DO, 8 AI, 3 AO — and a fourth pump 47 without anyone editing a schedule.

The calculation chart ​

The pump and system curves, with the duty points marked:

SeriesMeaning
pump, 1 pumpthe fitted pump curve at full speed, for the flow through one pump
pump, k pumpsthe same curve read at q/k — k identical pumps on a common main share the total flow
systemstatic head plus the rising main's friction, over the total flow

Faults you can inject ​

GroupCases
Level transmitterfails · frozen · reads 0.5 m high
FloatsLSHH fails · LSHH stuck on · LSLL fails · LSLL stuck on
Pumpsduty trips · duty fails to start · duty blocked
Flow meterfails · reads zero
Supplypower failure (2 h)

A fault whose device is not fitted is not offered, so a station with no flow meter has two cases fewer. Fault names follow the station's area number — a station at area 2 names its duty-trip case against P-201.

Honest limits ​

  • The run verdict and the design findings are shown on the workspace's Validation view; the single-fault suite is not run from it.
  • The 1,680-combination configuration matrix and the single-fault suite are release gates run as automated tests, not as something you can start from the workspace.
  • Nobody has recorded watching this unit run in a browser. The models are heavily tested; the on-screen behaviour of a run is not described here.